Supply air, return air and USDA probes in reefer container cold treatment
During cold treatment the reefer unit controls the air, but the treatment is judged on the pulp. This guide brings together how cold treatment is activated on each brand, what authorities require for containers, where the probes go according to Carrier and APHIS and what research says about the link between air and fruit.
🌐 Español
How the unit controls temperature
- Supply air: in perishable mode Carrier controls on the supply probe and keeps that air within ±0.25 °C of setpoint (Carrier ThinLINE manual). Hapag-Lloyd states the same for setpoints above −10 °C (Hapag-Lloyd LIVE FAQ).
- Return air: picks up the heat of the cargo, heat entering through the insulation and defrost heat; respiring fruit also raises it (Hapag-Lloyd).
- Difference between them: with fruit warmer than setpoint, the air warms up strongly as it passes through the load; as the load cools down, the supply/return differential narrows (West P&I, The Carriage of Reefer Containers).
- What the unit records: recorders store air temperatures; cargo temperature is only recorded when USDA probes are connected (West P&I).
1. How to activate cold treatment on each brand
| Brand | Function | Where it is set | Main parameters |
|---|---|---|---|
| Carrier | ACT (Automatic Cold Treatment) | Function code Cd51 | Treatment temperature, days, probes, final setpoint |
| Thermo King | CT (Cold Treatment), MP4000 controller | Configuration › Options › CT Feature; then Setpoint/Control › Cold Treatment | CT setpoint, period, USDA max, final setpoint |
| Star Cool | ACT (Automatic Cold Treatment program), CIM 6 controller | Operation › PROGRAMS › Auto Cold Treatment; activated in P01 | Duration, treatment limit, treatment setpoint, new setpoint |
| Daikin | ACT (Automatic Cold Treatment, optional), LX10F inverter | MENU › Mode Set › Automatic Cold Treatment | CT days, USDA max, setpoint, final setpoint |
Carrier (OptimaLINE / PrimeLINE, Micro-Link 5): ACT with Cd51
- Enter the cargo setpoint. It must be lower than the treatment temperature.
- Press CODE SELECT, scroll to Cd51 and press ENTER.
- Select "On" and press ENTER.
- Set the treatment temperature (the maximum value the USDA probes must stay below) and press ENTER.
- Set the number of treatment days and press ENTER.
- Confirm the connected probe numbers shown on the display and press ENTER.
- Set the setpoint the unit will use after the treatment and press ENTER.
- Cd51 shows a countdown in days and hours. The countdown starts once all detected USDA probes reach the treatment temperature.
- ACT requires at least 3 USDA probes configured and detected; ACT and Automatic Setpoint Change (ASC, Cd53) cannot run at the same time, and ACT turns off when a Pre-Trip or Trip Start begins (Carrier T-383, section 4; Carrier T-383, section 5).
- Calibration: the DataLINE software calibrates the USDA probes in an ice bath stabilized at 0 °C; the controller calibrates once readings are stable (Carrier DataLINE, section 10).
- Technical notice, August 2026: with software 6332 there were cases of the setpoint changing to 0.0 °C after a power cycle during treatment. Carrier advises not to use 6332 on units running ACT, approves OptimaLINE 7103 and PrimeLINE 5394 for ACT, and asks to keep power-saving modes off (Cd34, Cd63, Cd50) (Carrier notice TL008-2026).
Thermo King (MAGNUM PLUS, MP4000): CT function
- Enable: Configuration › Options › CT Feature › ON.
- Calibrate: immerse all USDA probes in an ice bath; in CONFIG › Calibration › CALIBRATE PROBES, release the current offsets and accept the new ones once all probes read between +0.3 °C and −0.3 °C and have been stable for five minutes.
- Start: Setpoint/Control › Cold Treatment (CT), enter the load settings and select EXIT. The display shows "CT In Progress".
- Parameters: CT setpoint (used during the period), period in days, USDA max (maximum allowed probe reading) and final setpoint. The manual example uses CT setpoint 1.0 °C, USDA max 3.0 °C, 3 days and final setpoint 5.0 °C.
- The period starts once all USDA probes drop to or below USDA max; if any goes above it, the period is cancelled and restarts. When it ends, the setpoint rises 0.1 °C per hour up to the final setpoint.
- If one or more probes fail, the period continues and the failure is logged; if all three fail, the period continues on time only (Thermo King manual, Cold Treatment (CT); standard USDA recording).
Star Cool (MCI, CIM 6 controller): ACT program
- Calibrate: place the USDA and cargo probes in an ice bath; they must read 0 °C. If one deviates, correct it with the StarView software (CalUs1, CalUs2, CalUs3). Maximum offset is 3 K; if more is needed, replace the probe.
- Connect the USDA probes in the cargo. ACT only starts if all of them work; a reading of −70 °C means a probe is not connected.
- Press the Operation key and go to PROGRAMS › Auto Cold Treatment.
- Enter the values. For each one: move to the line with the arrows, press Enter, change the value with the arrows and hold Enter for 3 seconds to accept it.
B01 Duration: 1 to 45 days. B02 Treatment limit (maximum allowed USDA probe temperature): −4.7 to +30.0 °C. B03 Treatment setpoint: from −4.9 °C up to 0.2 K below the limit. B04 New setpoint after treatment: −1.5 to +30.0 °C. - Activate: in P01 Active program select ACT and hold Enter for 3 seconds. The display shows the ACT icon.
- Check: B05 shows the status (Not active, Active, Aborted, Pass, Done or Fail). When finished without failures it shows "ACT PASSED"; if probes are out of range, "ACT FAILED".
- Day counting starts once at least 3 USDA probes are below the limit. If a probe exceeds the limit and comes back down, the count restarts.
- After activation, B02 and B04 are locked; B03 can be adjusted within its range. If one or more USDA probes fail, the treatment setpoint is kept for the rest of the trip. During ACT the datalog interval is fixed at 60 minutes.
- ACT only ends when P01 is set to None, a PTI is started or the unit is without power for more than 48 hours (168 hours depending on prefix) (Star Cool manual 810900E, sections 11.13.2 and 22.11).
- A CIM 6 controller update made sure ACT correctly fails when USDA probes are above the limit (MCI release note 035806).
Daikin (LX10F inverter, DECOS Va controller): ACT
- Set the USDA probes: choose 3, 4 (3 USDA probes and 1 cargo sensor), AUTO or OFF; for cold treatment, the number the protocol requires. ACT does not work if USDA is OFF or the ACT option is disabled in the optional functions.
- Check the probe type: 1 = ST9702-1, 2 = NTC (standard). A wrong type gives very different values at calibration.
- Calibrate the USDA probes before each trip with a PC and Daikin's DCCS software.
- On the operation screen press MENU › Mode Set › Automatic Cold Treatment, select ON with ▲▼ and press ENTER.
- Enter the four values: USDA CT days (1 to 99 days), USDA Max. Temperature (maximum pulp temperature, −4.9 to 30.0 °C), Setpoint during treatment and Final-SP after treatment (both −4.9 to 30.0 °C). Manual example: 10 days, max 1.0 °C, setpoint 0.0 °C and final 3.0 °C.
- At "Press Enter to Start" press ENTER (ESC cancels). The SET-MODE area shows "ACT", alternating every 5 seconds with "USDA INFO"; ▲▼ shows remaining days and status (ACTIVE).
- Counting starts once all USDA probes drop below USDA max. If one exceeds it, the event is logged and, when it drops again, the days are counted from zero.
- During ACT the setpoint and final setpoint can be changed, but not the days or USDA max. When it ends, the setpoint rises 0.1 °C per hour.
- Power loss: under 1 hour, it continues; 1 to 48 hours, the count restarts; 48 to 72 hours, it continues at the final setpoint; 72 hours or more, it is cancelled. It is also cancelled by setting ACT to OFF or completing a PTI (Daikin service manual TR 16-02, sections 1.5.3 and 2.3).
- LXE10E units (DECOS III): the number of probes is set in the optional function mode (OFF, 3 or 4) and confirmed by switching the breaker off; the "Au" option is not valid for cold treatment. Calibration and the USDA report are done with DCCS ("USDA SENSOR CALIBRATION" and "USDA TREATMENT REPORT") (Daikin LXE10E manual, section 4.1).
2. What authorities require for cold treatment in reefer containers
| Authority | Probes | When it starts / when it fails | Other requirements |
|---|---|---|---|
| USA (APHIS, 7 CFR 305.6) | At least 3 pulp probes | Starts when all probes reach the schedule temperature. Invalidated if pulp varies more than 0.39 °C between two hourly readings or if records have gaps longer than 1 hour, unless APHIS verifies it. | Precooled fruit; at loading the inspector checks pulp temperatures and rejects a pallet if the fruit is 0.28 °C or more above the schedule. Recording at least hourly. Numbered seal on the doors. One fruit and one package type per container. |
| China (example: citrus protocol with South Africa) | 3 fruit sensors and 2 air sensors (supply and return) | Treatment time counts once all fruit sensors reach the set temperature. | Sensors accurate to ±0.1 °C between −3 and +3 °C; a sensor more than ±0.3 °C from 0 °C at calibration is replaced. |
| Japan (container protocol) | At least 3 pulp sensors; 1 air sensor in supply and 1 in return | — | Supply air is controlled to keep the fruit core temperature in range. Fixed probe positions in the first pallet, the center and the last pallet. |
| European Union (Regulation 2022/959, oranges) | As per ISPM 42 | Pulp precooled to the treatment temperature, then at least 20 days at a set temperature between −1 °C and +2 °C. | In-transit treatment records available on request. |
| Australia (DAFF, as exporting country) | Normally 3 sensors | Start time is recorded once all sensors are below the nominated temperature. | Ice calibration; each sensor within ±0.3 °C of 0 °C with identical repeat readings; correction factor recorded; container clock on GMT ±5 minutes; cable secured so the probe cannot pull out. |
Sources: 7 CFR 305.6 (USA) · South Africa–China protocol · Japan requirements (official document) · Regulation (EU) 2022/959 · DAFF Australia ITCT work instruction.
3. Where the USDA probes go (Carrier and APHIS)

- Probe 1: in the pulp of product located next to the return air intake, i.e. at the top and against the refrigeration unit.
- Probe 2: five feet from the end of the load in 40 ft containers, or three feet in 20 ft containers, in a center carton at half the height of the load.
- Probe 3: the same distance from the end of the load, in a carton at a side wall, at half height.
What APHIS says (US program)
The APHIS Treatment Manual uses a different layout for a 40 ft container with 18 pallets (APHIS Treatment Manual, ch. 3-7):

| Probe | Carrier (unit manual) | APHIS (Treatment Manual) |
|---|---|---|
| USDA 1 | Next to the return air intake | In a box at the top of the stack, as close as possible to the return air intake |
| USDA 2 | 5 ft from the end of the load, center carton, mid-height | Slightly toward the doors from the middle of the container, halfway up the stack |
| USDA 3 | 5 ft from the end of the load, against the side wall, mid-height | One pallet in from the doors, halfway up the stack |
- How to insert: the probe goes well into the fruit, without the tip coming out the other side. With small fruit such as grapes, several pieces are threaded onto the probe to cover at least two thirds of the tip, under the top layer in the middle of the pallet. The opened carton is resealed with tape.
- Loading: the warmest fruit goes in the last quarter, near the doors, and the load must be even in floor coverage and height. In the last row, cardboard is laid on the floor up to the doors and a second piece is stapled upright to the cartons to improve airflow. The doors carry a numbered seal until clearance at destination.
- More probes than the minimum: APHIS recommends them. If one fails, it can only be disregarded if another one is working and all were properly placed and calibrated; otherwise the treatment is repeated.
- Who does what: the reefer technician calibrates and installs the probes before shipment, and the APHIS-authorized official checks the calibration values and the probe locations (APHIS Treatment Manual).
Each protocol may set its own positions. Japan, for example, asks for probe 1 in the second layer from the top of the first pallet, probe 2 in a pallet at mid-height near the container centerline and probe 3 in the last pallet, second layer from the bottom (Japan requirements). Always check the destination work plan before loading. For inserting the probe into the fruit, see the USDA probe placement guide.
4. What research shows about air and pulp
- Pulp takes days to come down. In citrus loaded without precooling, fruit reached 3 °C only after 5 to 6 days, and one container cooled less evenly due to poor airflow distribution (Berry et al., Acta Horticulturae 1275). That is why protocols require precooled fruit.
- Correct air does not guarantee even pulp. A case study of the South African fruit export chain cites work in which supply air stayed close to setpoint, yet there were significant temperature differences between pallet positions (Journal of Transport and Supply Chain Management).
- Probes may miss some spots. With about three pulp sensors, a localized hot or cold spot, for example at the bottom of the first pallets near the unit, may not show in the data; the authors recommend extra probes there during cooling (engrXiv preprint on hot spots in reefer containers).
- "Virtual fruit" models. Researchers from Empa, Stellenbosch and Wageningen feed digital twins with supply air data from real shipments to estimate fruit temperature and quality at each position; they found small quality differences within a container and large ones between containers (Wageningen University & Research).
- Active setpoint control. A patent describes a controller that adjusts the unit setpoint, for example by 0.2 or 0.3 °C, according to changes detected by the USDA probes, and restarts the treatment if the maximum is exceeded (US patent 12188700).
For pulp readings to be reliable, the probes must be calibrated in a well-prepared ice bath: see the ice bath calibration technical note. USDA PROBE manufactures compatible USDA probes for Carrier, Thermo King, Star Cool and Daikin controllers.
Note: this guide summarizes public documentation from manufacturers, carriers, authorities and researchers. It does not replace the unit manual or the official protocol in force at destination. USDA PROBE is an independent manufacturer, not affiliated with USDA or with Carrier, Thermo King, Star Cool or Daikin; brands are mentioned only to indicate compatibility. Updated: November 2026.
Frequently asked questions
Which sensor controls the unit during cold treatment?
In chill mode the controller regulates on the supply air sensor. USDA probes do not control the unit: they record the pulp and decide whether the treatment starts, restarts or ends.
Must the setpoint be lower than the treatment temperature?
Yes. In Carrier ACT the cargo setpoint must be lower than the treatment temperature, and in Thermo King CT the CT setpoint is below USDA max.
Can supply air be used instead of pulp temperature?
Not for containers. ISPM 42 and the authorities measure fruit temperature. Air is recorded as a control.
When does the treatment time start?
When all pulp probes reach the schedule temperature. If one rises above the limit, depending on the protocol and brand, the count restarts.
How many USDA probes are needed?
At least 3 pulp probes per container for the USA. China and Japan also require air sensors in supply and return.
Sources
- Carrier T-383 – Operation (ACT, Cd51)
- Carrier T-383 – Microprocessor and codes
- Carrier DataLINE – USDA probe calibration
- Carrier – Notice TL008-2026 (software 6332 and ACT)
- Carrier – USDA sensor placement (manual)
- Carrier ThinLINE – Supply air control
- Thermo King – Cold Treatment (CT), MP4000
- Thermo King – USDA recording
- MCI Star Cool – Release note 035806
- Star Cool – Operating and service manual 810900E
- Daikin LXE10E – Service manual TR 08-03C (cold treatment)
- Daikin LX10F inverter – Service manual TR 16-02 (ACT)
- Hapag-Lloyd – LIVE FAQ (supply and return air)
- West P&I – The Carriage of Reefer Containers
- USA – 7 CFR 305.6
- South Africa–China citrus protocol
- Japan requirements for containers
- DAFF Australia – ITCT work instruction
- Regulation (EU) 2022/959
- USDA APHIS – Treatment Manual, ch. 3-7 (cold treatment)
- FreshPlaza – Air vs pulp dispute (2022)
- Berry et al. – Ambient loading of citrus
- JTSCM – Temperature breaks in the export cold chain
- engrXiv – A hidden hot spot in reefer containers?
- WUR – Quality heterogeneity within and between containers
- US patent 12188700 – Active response cold treatment