How to place USDA probes in a reefer container for cold treatment
A practical guide for reefer technicians, inspectors and exporters: container preparation, calibration, inserting probes into the fruit and placement in the load.
🌐 Español · Português · Français
1. Prepare the container
- Check that the container number matches the treatment documentation.
- Check that the container is clean, free of pests and soil, with no structural damage and with intact door seals.
- Mesh drain holes, air intakes and vents so no gap is larger than 1.6 mm (Australian requirement).
- Set the controller clock to GMT, within five minutes (Australian requirement).
2. Calibrate the probes
Each probe is calibrated before loading with the ice slurry method. Readings are taken until they stabilize, and each probe’s reading and correction factor are recorded on the calibration record. Step by step in our ice-bath calibration technical note.
3. How many probes
APHIS cold treatment rules require a minimum of three temperature probes or sensors per treatment enclosure, such as a container, and four for vessel holds. In reefer containers, these three probes are the ones connected to the controller’s USDA 1, USDA 2 and USDA 3 channels.
4. Where they go
| Probe | Usual position |
|---|---|
| USDA 1 | Towards the front of the container, near the refrigeration unit |
| USDA 2 | In the middle of the load |
| USDA 3 | Towards the container doors |
This front–middle–rear layout is the one used in practice. Some protocols also require a specific height, for example halfway up the stack; always follow the destination’s protocol.
5. Insert the probe into the fruit
- The tip goes into the pulp and is covered by product as much as possible, without sticking out.
- With small fruit such as grapes or cherries, several pieces are placed on the probe to cover it.
- The fruit with the probe goes back into its carton, and the pulp temperature is recorded once stable.
- The cable spool is taped to the outside of the carton and the running end is secured so the probe is not pulled out when the pallet moves.
6. Mistakes that put the treatment at risk
- Fruit not precooled: the treatment does not start counting until pulp reaches the schedule temperature.
- Probe not calibrated, or correction factor not recorded.
- Probe tip in the air or touching the carton: it measures air, not pulp.
- Cable under tension or crushed: the probe comes out or is cut during the voyage.
Need replacement probes? Our probes are compatible with Carrier, Thermo King, Star Cool and Daikin, with 15 m of cable and a 3-year warranty. Request a quotation.
Frequently asked questions
How many USDA probes does a cold treatment container use?
At least three, one per USDA channel on the controller, under APHIS rules. The destination protocol may require more.
Where does each probe go?
Usually one towards the front (near the refrigeration unit), one in the middle and one towards the doors, at the height the protocol specifies.
Do probes need calibrating before each load?
Yes. They are calibrated in an ice bath and each probe’s correction factor is recorded on the calibration record.